상세 보기
실별제어 난방 시스템의 부분부하 효율 향상을 위한 바이패스 히팅 시스템 성능 평가
- 이규남;
- 송진환;
- 류성룡
초록
In this study, a bypass heating system was suggested to improve the part load efficiency of individual room control for residential heating systems. TRNSYS simulation model for the suggested system was developed and heating energy consumption was analyzed to examine the practical applicability. The system was represented with 3-way valves, small circulation pump, and electric heater, which operates under part load condition that water temperature difference becomes less than 10℃. Simulation results showed that the heating energy consumption was reduced by 60% under the aforementioned part load condition. During the whole heating season, the bypass heating system operated for 342 hours, while the operation time of the boiler was reduced by 19.6%. Consequently, heating and pumping energy was reduced by 4.02% and 15.1%, respectively, which resulted in the overall energy saving by 4.12%.
키워드
- 제목
- 실별제어 난방 시스템의 부분부하 효율 향상을 위한 바이패스 히팅 시스템 성능 평가
- 제목 (타언어)
- Performance Evaluation of Bypass Heating System to Improve Part Load Efficiency of Individual Room Control Heating System
- 저자
- 이규남; 송진환; 류성룡
- 발행일
- 2021-12
- 저널명
- 한국건축친환경설비학회 논문집
- 권
- 15
- 호
- 6
- 페이지
- 735 ~ 746
- 언어
- KOR
- 출판사
- 한국건축친환경설비학회
- 발행국가
- 대한민국
- 분량
- 12 페이지
- ISSN
- E 2586-0666
P 1976-6483